Performance Test |
![]() |
![]() The fan arrangment used during the performance test |
Curtain
wall mock up panel
The
performance tests which are usually of greatest concern and structual performance
under wind loading and the ability of the wall to prevent water penetratiion
during heavy rain storms. These represent two levels of concern.
Structural failure, of course, may endanger human life, so structural adequacy
is a basic essential. The occurrence of water leakage will not likely
be dangerous, but may cause discomfort and substantial property damage.
The concern about air leakage is though the amount of air passing through
the wall must always be limited to a small amout in order to minimize heat
loss and condensation. Tests included:
![]() |
Preload | ||||||||||||||||||||||||
The testing sample was preloaded to 50% of the design positive pressure for 10 second in order to preset and provide a settling and take up period for the system. | |||||||||||||||||||||||||
![]() |
Air Infiltration Test to ASTM E283-91 | ||||||||||||||||||||||||
A static 300 Pa positive pressure was applied.
Air infiltration through the sample shall not exceed 0.02m3/min/m2 |
|||||||||||||||||||||||||
![]() |
Water Penetration Test under Static Pressure to ASTM E331-93 | ||||||||||||||||||||||||
A 4 minutes pre soaking period, should be applied at
zero pressure and then a static 1000 Pa positive pressure was applied for
15 minutes.
In the test, water should not appear on the interior side of the plane of the innermost face of the test sample. |
|||||||||||||||||||||||||
![]() |
Water Penentration Test under Cyclic Pressure AS/NZS 4284-1995 | ||||||||||||||||||||||||
The following cyclic pressures were applied and water
spray operated all the time.
Water should not be appear on the interior side of the plane of the intermost face of the test sample. |
|||||||||||||||||||||||||
![]() |
Strutural Adequacy Test under Static Pressure to ASTM E330-90 | ||||||||||||||||||||||||
The test specimen was tested under design prositive and
negative pressure in following stages:
Under these loading conditions, the test specimen should meet the following criteria:
|
|||||||||||||||||||||||||
![]() |
Structural Adequacy Test under Cyclic Load to Hong Kong Building Department PNAP 106 Cyclic | ||||||||||||||||||||||||
The test specimen was tested under the following sequence
for positive and negative pressure successively:
Readings were taken at the beginning, at the end, and during the P2 loading. After the safety test, 15 minutes were allowed for the specicman to settle before taking readings when the was unloaded. The test specimen should met the following criteria:
|
|||||||||||||||||||||||||
![]() |
Safety/Proof Test | ||||||||||||||||||||||||
The test specimen was to be tested up to 150% of the
design positive and negative pressure under static. The following
load sequence was applied:
The test specimen should met the following criteria:
|